{"affected":[{"affectedData":[{"product":"InfraSuite Device Master","vendor":"Delta Electronics","versions":[{"lessThan":"1.0.5","status":"affected","version":"0","versionType":"custom"}]}],"source":"ics-cert@hq.dhs.gov"}],"configurations":[{"nodes":[{"cpeMatch":[{"criteria":"cpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:*","matchCriteriaId":"CCCA3760-38A4-4DBF-98D3-1A6799317836","versionEndExcluding":"1.0.5","vulnerable":true}],"negate":false,"operator":"OR"}]}],"cveTags":[],"descriptions":[{"lang":"en","value":"Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code."}],"id":"CVE-2023-1133","lastModified":"2026-06-17T05:27:11.563","metrics":{"cvssMetricV31":[{"cvssData":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":9.8,"baseSeverity":"CRITICAL","confidentialityImpact":"HIGH","integrityImpact":"HIGH","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","version":"3.1"},"exploitabilityScore":3.9,"impactScore":5.9,"source":"ics-cert@hq.dhs.gov","type":"Secondary"},{"cvssData":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":9.8,"baseSeverity":"CRITICAL","confidentialityImpact":"HIGH","integrityImpact":"HIGH","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","version":"3.1"},"exploitabilityScore":3.9,"impactScore":5.9,"source":"nvd@nist.gov","type":"Primary"}],"ssvcV203":[{"source":"134c704f-9b21-4f2e-91b3-4a467353bcc0","ssvcData":{"id":"CVE-2023-1133","options":[{"exploitation":"none"},{"automatable":"yes"},{"technicalImpact":"total"}],"role":"CISA Coordinator","timestamp":"2025-01-16T20:58:50.636236Z","version":"2.0.3"}}]},"published":"2023-03-27T15:15:07.293","references":[{"source":"ics-cert@hq.dhs.gov","url":"http://packetstormsecurity.com/files/172799/Delta-Electronics-InfraSuite-Device-Master-Deserialization.html"},{"source":"ics-cert@hq.dhs.gov","tags":["Third Party Advisory","US Government Resource"],"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-23-080-02"},{"source":"af854a3a-2127-422b-91ae-364da2661108","url":"http://packetstormsecurity.com/files/172799/Delta-Electronics-InfraSuite-Device-Master-Deserialization.html"},{"source":"af854a3a-2127-422b-91ae-364da2661108","tags":["Third Party Advisory","US Government Resource"],"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-23-080-02"}],"sourceIdentifier":"ics-cert@hq.dhs.gov","vulnStatus":"Modified","weaknesses":[{"description":[{"lang":"en","value":"CWE-502"}],"source":"nvd@nist.gov","type":"Primary"}]}