Files
vuln-cve/data/2026/59xxx/CVE-2026-59693.json
T

177 lines
6.9 KiB
JSON

{
"dataType": "CVE_RECORD",
"dataVersion": "5.2",
"cveMetadata": {
"cveId": "CVE-2026-59693",
"assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
"state": "PUBLISHED",
"assignerShortName": "siemens",
"dateReserved": "2026-07-06T13:50:39.917Z",
"datePublished": "2026-08-11T12:20:26.209Z",
"dateUpdated": "2026-08-11T18:08:58.835Z"
},
"containers": {
"cna": {
"providerMetadata": {
"orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
"shortName": "siemens",
"dateUpdated": "2026-08-11T12:20:26.209Z"
},
"descriptions": [
{
"lang": "en",
"value": "A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality."
}
],
"affected": [
{
"vendor": "Siemens",
"product": "Desigo DXR2",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V01.21.233.16-7862",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
},
{
"vendor": "Siemens",
"product": "Desigo PXC3",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V01.21.233.16-7862",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
},
{
"vendor": "Siemens",
"product": "Desigo PXC4",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V02.21.194.36-2715",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
},
{
"vendor": "Siemens",
"product": "Desigo PXC5.E003",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V02.21.194.36-2715",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
},
{
"vendor": "Siemens",
"product": "Desigo PXC5.E24",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V02.21.194.36-2715",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
},
{
"vendor": "Siemens",
"product": "Desigo PXC7",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V02.21.194.36-2715",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
}
],
"metrics": [
{
"cvssV3_1": {
"version": "3.1",
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L",
"baseScore": 4.3,
"baseSeverity": "MEDIUM"
}
},
{
"cvssV4_0": {
"version": "4.0",
"vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N",
"baseScore": 5.3,
"baseSeverity": "MEDIUM"
}
}
],
"problemTypes": [
{
"descriptions": [
{
"lang": "en",
"cweId": "CWE-754",
"description": "CWE-754: Improper Check for Unusual or Exceptional Conditions",
"type": "CWE"
}
]
}
],
"references": [
{
"url": "https://cert-portal.siemens.com/productcert/html/ssa-781903.html"
}
]
},
"adp": [
{
"metrics": [
{
"other": {
"type": "ssvc",
"content": {
"timestamp": "2026-08-11T18:08:48.569650Z",
"id": "CVE-2026-59693",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
}
],
"title": "CISA ADP Vulnrichment",
"providerMetadata": {
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP",
"dateUpdated": "2026-08-11T18:08:58.835Z"
}
}
]
}
}