176 lines
7.2 KiB
JSON
176 lines
7.2 KiB
JSON
{
|
||
"dataType": "CVE_RECORD",
|
||
"dataVersion": "5.2",
|
||
"cveMetadata": {
|
||
"cveId": "CVE-2026-1773",
|
||
"assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17",
|
||
"state": "PUBLISHED",
|
||
"assignerShortName": "Hitachi Energy",
|
||
"dateReserved": "2026-02-02T16:28:59.394Z",
|
||
"datePublished": "2026-02-24T13:13:17.990Z",
|
||
"dateUpdated": "2026-05-27T14:50:01.447Z"
|
||
},
|
||
"containers": {
|
||
"cna": {
|
||
"providerMetadata": {
|
||
"orgId": "e383dce4-0c27-4495-91c4-0db157728d17",
|
||
"shortName": "Hitachi Energy",
|
||
"dateUpdated": "2026-05-26T14:53:41.970Z"
|
||
},
|
||
"problemTypes": [
|
||
{
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"cweId": "CWE-184",
|
||
"description": "CWE-184 Incomplete List of Disallowed Inputs",
|
||
"type": "CWE"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"impacts": [
|
||
{
|
||
"capecId": "CAPEC-278",
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"value": "CAPEC-278 Web Services Protocol Manipulation"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"affected": [
|
||
{
|
||
"vendor": "Hitachi Energy",
|
||
"product": "RTU500 series CMU firmware",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "12.7.1",
|
||
"lessThanOrEqual": "12.7.7",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.5.1",
|
||
"lessThanOrEqual": "13.5.4",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.6.1",
|
||
"lessThanOrEqual": "13.6.2",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.7.1",
|
||
"lessThanOrEqual": "13.7.7",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.8.1",
|
||
"versionType": "custom"
|
||
}
|
||
],
|
||
"defaultStatus": "unaffected"
|
||
}
|
||
],
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.",
|
||
"supportingMedia": [
|
||
{
|
||
"type": "text/html",
|
||
"base64": false,
|
||
"value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.<br>"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"references": [
|
||
{
|
||
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000237&LanguageCode=en&DocumentPartId=&Action=Launch"
|
||
}
|
||
],
|
||
"metrics": [
|
||
{
|
||
"format": "CVSS",
|
||
"scenarios": [
|
||
{
|
||
"lang": "en",
|
||
"value": "GENERAL"
|
||
}
|
||
],
|
||
"cvssV4_0": {
|
||
"attackVector": "NETWORK",
|
||
"attackComplexity": "LOW",
|
||
"attackRequirements": "NONE",
|
||
"privilegesRequired": "NONE",
|
||
"userInteraction": "NONE",
|
||
"vulnConfidentialityImpact": "NONE",
|
||
"subConfidentialityImpact": "NONE",
|
||
"vulnIntegrityImpact": "NONE",
|
||
"subIntegrityImpact": "NONE",
|
||
"vulnAvailabilityImpact": "HIGH",
|
||
"subAvailabilityImpact": "NONE",
|
||
"exploitMaturity": "NOT_DEFINED",
|
||
"Safety": "NOT_DEFINED",
|
||
"Automatable": "NOT_DEFINED",
|
||
"Recovery": "NOT_DEFINED",
|
||
"valueDensity": "NOT_DEFINED",
|
||
"vulnerabilityResponseEffort": "NOT_DEFINED",
|
||
"providerUrgency": "NOT_DEFINED",
|
||
"version": "4.0",
|
||
"baseSeverity": "HIGH",
|
||
"baseScore": 8.7,
|
||
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N"
|
||
}
|
||
}
|
||
],
|
||
"source": {
|
||
"discovery": "UNKNOWN"
|
||
},
|
||
"x_generator": {
|
||
"engine": "Vulnogram 0.5.0"
|
||
}
|
||
},
|
||
"adp": [
|
||
{
|
||
"metrics": [
|
||
{
|
||
"other": {
|
||
"type": "ssvc",
|
||
"content": {
|
||
"timestamp": "2026-02-28T02:19:44.432868Z",
|
||
"id": "CVE-2026-1773",
|
||
"options": [
|
||
{
|
||
"Exploitation": "none"
|
||
},
|
||
{
|
||
"Automatable": "yes"
|
||
},
|
||
{
|
||
"Technical Impact": "partial"
|
||
}
|
||
],
|
||
"role": "CISA Coordinator",
|
||
"version": "2.0.3"
|
||
}
|
||
}
|
||
}
|
||
],
|
||
"title": "CISA ADP Vulnrichment",
|
||
"providerMetadata": {
|
||
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
||
"shortName": "CISA-ADP",
|
||
"dateUpdated": "2026-05-27T14:50:01.447Z"
|
||
}
|
||
}
|
||
]
|
||
}
|
||
} |