"dataType": "CVE_RECORD",
|
|
"dataVersion": "5.2",
|
|
"cveMetadata": {
|
|
"cveId": "CVE-2026-12819",
|
|
"assignerOrgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
|
|
"state": "PUBLISHED",
|
|
"assignerShortName": "Deltaww",
|
|
"dateReserved": "2026-06-21T10:18:28.804Z",
|
|
"datePublished": "2026-06-30T06:28:51.514Z",
|
|
"dateUpdated": "2026-06-30T12:50:59.070Z"
|
|
},
|
|
"containers": {
|
|
"cna": {
|
|
"providerMetadata": {
|
|
"orgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
|
|
"shortName": "Deltaww",
|
|
"dateUpdated": "2026-06-30T06:28:51.514Z"
|
|
},
|
|
"title": "DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability",
|
|
"datePublic": "2026-06-30T05:29:00.000Z",
|
|
"problemTypes": [
|
|
{
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"cweId": "CWE-306",
|
|
"description": "CWE-306 Missing Authentication for Critical Function",
|
|
"type": "CWE"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"impacts": [
|
|
{
|
|
"capecId": "CAPEC-115",
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CAPEC-115: Authentication Bypass"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"affected": [
|
|
{
|
|
"vendor": "deltaww",
|
|
"product": "DVP-12SE",
|
|
"versions": [
|
|
{
|
|
"status": "affected",
|
|
"version": "*"
|
|
}
|
|
],
|
|
"defaultStatus": "unaffected"
|
|
}
|
|
],
|
|
"cpeApplicability": [
|
|
{
|
|
"operator": "OR",
|
|
"nodes": [
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:deltaww:dvp-12se:*:*:*:*:*:*:*:*"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions.",
|
|
"supportingMedia": [
|
|
{
|
|
"type": "text/html",
|
|
"base64": false,
|
|
"value": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions."
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"references": [
|
|
{
|
|
"url": "https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2026-00011_DVP12SE%20Multiple%20Vulnerabilities%20(CVE-2026-12818,%20CVE-2026-12819)_v1.0.pdf"
|
|
}
|
|
],
|
|
"metrics": [
|
|
{
|
|
"format": "CVSS",
|
|
"scenarios": [
|
|
{
|
|
"lang": "en",
|
|
"value": "GENERAL"
|
|
}
|
|
],
|
|
"cvssV4_0": {
|
|
"attackVector": "NETWORK",
|
|
"attackComplexity": "LOW",
|
|
"attackRequirements": "NONE",
|
|
"privilegesRequired": "NONE",
|
|
"userInteraction": "NONE",
|
|
"vulnConfidentialityImpact": "HIGH",
|
|
"subConfidentialityImpact": "NONE",
|
|
"vulnIntegrityImpact": "HIGH",
|
|
"subIntegrityImpact": "NONE",
|
|
"vulnAvailabilityImpact": "HIGH",
|
|
"subAvailabilityImpact": "NONE",
|
|
"exploitMaturity": "NOT_DEFINED",
|
|
"Safety": "NOT_DEFINED",
|
|
"Automatable": "NOT_DEFINED",
|
|
"Recovery": "NOT_DEFINED",
|
|
"valueDensity": "NOT_DEFINED",
|
|
"vulnerabilityResponseEffort": "NOT_DEFINED",
|
|
"providerUrgency": "NOT_DEFINED",
|
|
"version": "4.0",
|
|
"baseSeverity": "CRITICAL",
|
|
"baseScore": 9.3,
|
|
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
|
|
}
|
|
}
|
|
],
|
|
"workarounds": [
|
|
{
|
|
"lang": "en",
|
|
"value": "Users are recommended to take the following mitigation measures:\n\n * Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\n * Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\n * Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.",
|
|
"supportingMedia": [
|
|
{
|
|
"type": "text/html",
|
|
"base64": false,
|
|
"value": "Users are recommended to take the following mitigation measures:\n<br><ul><li>Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n</li><li>Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n</li><li>Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel. </li></ul>"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"credits": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CISA",
|
|
"type": "coordinator"
|
|
},
|
|
{
|
|
"lang": "en",
|
|
"value": "Adm Bin Harbi (0xnoag) - Corvo Security",
|
|
"type": "reporter"
|
|
}
|
|
],
|
|
"source": {
|
|
"discovery": "UNKNOWN"
|
|
},
|
|
"x_generator": {
|
|
"engine": "Vulnogram 1.0.2"
|
|
}
|
|
},
|
|
"adp": [
|
|
{
|
|
"metrics": [
|
|
{
|
|
"other": {
|
|
"type": "ssvc",
|
|
"content": {
|
|
"timestamp": "2026-06-30T12:50:51.923347Z",
|
|
"id": "CVE-2026-12819",
|
|
"options": [
|
|
{
|
|
"Exploitation": "none"
|
|
},
|
|
{
|
|
"Automatable": "yes"
|
|
},
|
|
{
|
|
"Technical Impact": "total"
|
|
}
|
|
],
|
|
"role": "CISA Coordinator",
|
|
"version": "2.0.3"
|
|
}
|
|
}
|
|
}
|
|
],
|
|
"title": "CISA ADP Vulnrichment",
|
|
"providerMetadata": {
|
|
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
|
"shortName": "CISA-ADP",
|
|
"dateUpdated": "2026-06-30T12:50:59.070Z"
|
|
}
|
|
}
|
|
]
|
|
}
|
|
} |