"dataType": "CVE_RECORD",
"dataVersion": "5.2",
"cveMetadata": {
"cveId": "CVE-2026-124759",
"assignerOrgId": "4b71179a-3b92-4a9d-b9fc-af8b8ed579ee",
"state": "PUBLISHED",
"assignerShortName": "rt-labs",
"dateReserved": "2026-11-09T12:48:59.071Z",
"datePublished": "2026-11-13T13:22:56.820Z",
"dateUpdated": "2026-11-13T13:22:56.820Z"
},
"containers": {
"cna": {
"providerMetadata": {
"orgId": "4b71179a-3b92-4a9d-b9fc-af8b8ed579ee",
"shortName": "rt-labs",
"dateUpdated": "2026-11-13T13:22:56.820Z"
},
"title": "Alarm frames are accepted from any source address",
"problemTypes": [
{
"descriptions": [
{
"lang": "en",
"cweId": "CWE-346",
"description": "CWE-346 Origin Validation Error",
"type": "CWE"
}
]
}
],
"affected": [
{
"vendor": "RT-Labs",
"product": "P-Net",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "1.0.4",
"versionType": "semver"
},
{
"status": "affected",
"version": "1.0.4",
"lessThan": "*",
"versionType": "semver"
}
],
"defaultStatus": "unaffected"
}
],
"descriptions": [
{
"lang": "en",
"value": "P-Net before 1.0.4 routes a received RTA alarm frame to an Application Relationship using only the destination alarm reference in the frame, without checking the source of the frame. A host with ADJACENT network access can abort an established Application Relationship with a single alarm ERROR frame, or deliver forged alarm notifications with chosen type, slot, subslot, USI and payload to the application.",
"supportingMedia": [
{
"type": "text/html",
"base64": false,
"value": "<p>P-Net before 1.0.4 routes a received RTA alarm frame to an Application Relationship using only the destination alarm reference in the frame, without checking the source of the frame. A host with ADJACENT network access can abort an established Application Relationship with a single alarm ERROR frame, or deliver forged alarm notifications with chosen type, slot, subslot, USI and payload to the application.</p>"
}
]
}
],
"references": [
{
"url": "https://rt-labs.com/wp-content/uploads/2026/11/RRTL-261109-01.pdf",
"name": "Cybersecurity advisory for P-Net"
}
],
"metrics": [
{
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
],
"cvssV4_0": {
"attackVector": "ADJACENT",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"privilegesRequired": "NONE",
"userInteraction": "NONE",
"vulnConfidentialityImpact": "NONE",
"subConfidentialityImpact": "NONE",
"vulnIntegrityImpact": "LOW",
"subIntegrityImpact": "NONE",
"vulnAvailabilityImpact": "HIGH",
"subAvailabilityImpact": "NONE",
"exploitMaturity": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"valueDensity": "NOT_DEFINED",
"vulnerabilityResponseEffort": "NOT_DEFINED",
"providerUrgency": "NOT_DEFINED",
"version": "4.0",
"baseSeverity": "HIGH",
"baseScore": 7.1,
"vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N"
}
}
],
"solutions": [
{
"lang": "en",
"value": "Upgrade to P-Net 1.0.4 or later, which ignores alarm frames that do not come from the IO-controller of the Application Relationship. It reduces the risk but does not remove it, see Remaining Risk.",
"supportingMedia": [
{
"type": "text/html",
"base64": false,
"value": "<p>Upgrade to P-Net 1.0.4 or later, which ignores alarm frames that do not come from the IO-controller of the Application Relationship. It reduces the risk but does not remove it, see Remaining Risk.</p>"
}
]
}
],
"credits": [
{
"lang": "en",
"value": "Aditya Gupta (Attify - attify.com)",
"type": "finder"
}
],
"source": {
"discovery": "UNKNOWN"
},
"workarounds": [
{
"lang": "en",
"value": "Isolate the network of the device from untrusted hosts, for example by a firewall or a separate network,. The remaining risk is that a host on the network that knows the MAC address of the IO-controller and the alarm references can still send forged alarm frames.",
"supportingMedia": [
{
"type": "text/html",
"base64": false,
"value": "<p>Isolate the network of the device from untrusted hosts, for example by a firewall or a separate network,. The remaining risk is that a host on the network that knows the MAC address of the IO-controller and the alarm references can still send forged alarm frames.</p>"
}
]
}
]
}
}
}