Files
vuln-cve/data/2025/9xxx/CVE-2025-9364.json
T

154 lines
6.5 KiB
JSON
Raw Blame History

This file contains invisible Unicode characters
This file contains invisible Unicode characters that are indistinguishable to humans but may be processed differently by a computer. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
{
"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"cveMetadata": {
"cveId": "CVE-2025-9364",
"assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
"state": "PUBLISHED",
"assignerShortName": "Rockwell",
"dateReserved": "2025-08-22T15:52:49.830Z",
"datePublished": "2025-09-09T12:41:23.124Z",
"dateUpdated": "2025-09-09T13:36:31.291Z"
},
"containers": {
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "FactoryTalk® Analytics™ LogixAI®",
"vendor": "Rockwell Automation",
"versions": [
{
"status": "affected",
"version": "Versions 3.00 and 3.01"
}
]
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "<span style=\"background-color: rgb(255, 255, 255);\">An open database issue exists in the affected product and version. The security issue stems from an over permissive Redis instance. This could result in an attacker on the intranet accessing sensitive data and potential alteration of data.</span><span style=\"background-color: rgb(255, 255, 255);\">&nbsp;</span>"
}
],
"value": "An open database issue exists in the affected product and version. The security issue stems from an over permissive Redis instance. This could result in an attacker on the intranet accessing sensitive data and potential alteration of data."
}
],
"metrics": [
{
"cvssV4_0": {
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"attackVector": "ADJACENT",
"baseScore": 8.7,
"baseSeverity": "HIGH",
"privilegesRequired": "NONE",
"providerUrgency": "NOT_DEFINED",
"subAvailabilityImpact": "NONE",
"subConfidentialityImpact": "NONE",
"subIntegrityImpact": "NONE",
"userInteraction": "NONE",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
"version": "4.0",
"vulnAvailabilityImpact": "HIGH",
"vulnConfidentialityImpact": "HIGH",
"vulnIntegrityImpact": "HIGH",
"vulnerabilityResponseEffort": "NOT_DEFINED"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-497",
"description": "CWE-497: Exposure of Sensitive System Information to an Unauthorized Control Sphere",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"orgId": "b73dd486-f505-4403-b634-40b078b177f0",
"shortName": "Rockwell",
"dateUpdated": "2025-09-09T12:41:24.092Z"
},
"references": [
{
"url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1748.html"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Upgrade to&nbsp;\n\n<span style=\"background-color: rgb(255, 255, 255);\">Version 3.02 and later</span><span style=\"background-color: rgb(255, 255, 255);\">&nbsp;</span>"
}
],
"value": "Upgrade to \n\nVersion 3.02 and later"
}
],
"source": {
"advisory": "SD1748",
"discovery": "INTERNAL"
},
"title": "Rockwell Automation FactoryTalk® Analytics™ LogixAI® Exposed Redis DB",
"x_generator": {
"engine": "Vulnogram 0.2.0"
}
},
"adp": [
{
"metrics": [
{
"other": {
"type": "ssvc",
"content": {
"timestamp": "2025-09-09T13:36:25.672379Z",
"id": "CVE-2025-9364",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
}
],
"title": "CISA ADP Vulnrichment",
"providerMetadata": {
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP",
"dateUpdated": "2025-09-09T13:36:31.291Z"
}
}
]
}
}