"dataType": "CVE_RECORD",
|
|
"dataVersion": "5.1",
|
|
"cveMetadata": {
|
|
"cveId": "CVE-2025-40555",
|
|
"assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
|
|
"state": "PUBLISHED",
|
|
"assignerShortName": "siemens",
|
|
"dateReserved": "2025-04-16T08:20:17.029Z",
|
|
"datePublished": "2025-05-13T09:38:50.440Z",
|
|
"dateUpdated": "2025-05-13T13:25:06.076Z"
|
|
},
|
|
"containers": {
|
|
"cna": {
|
|
"providerMetadata": {
|
|
"orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
|
|
"shortName": "siemens",
|
|
"dateUpdated": "2025-05-13T09:38:50.440Z"
|
|
},
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation."
|
|
}
|
|
],
|
|
"affected": [
|
|
{
|
|
"vendor": "Siemens",
|
|
"product": "APOGEE PXC+TALON TC Series (BACnet)",
|
|
"versions": [
|
|
{
|
|
"status": "affected",
|
|
"version": "0",
|
|
"lessThan": "*",
|
|
"versionType": "custom"
|
|
}
|
|
],
|
|
"defaultStatus": "unknown"
|
|
}
|
|
],
|
|
"metrics": [
|
|
{
|
|
"cvssV3_1": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:L",
|
|
"baseScore": 4.7,
|
|
"baseSeverity": "MEDIUM"
|
|
}
|
|
},
|
|
{
|
|
"cvssV4_0": {
|
|
"version": "4.0",
|
|
"vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:L",
|
|
"baseScore": 5.3,
|
|
"baseSeverity": "MEDIUM"
|
|
}
|
|
}
|
|
],
|
|
"problemTypes": [
|
|
{
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"cweId": "CWE-440",
|
|
"description": "CWE-440: Expected Behavior Violation",
|
|
"type": "CWE"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"references": [
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/html/ssa-718393.html"
|
|
}
|
|
]
|
|
},
|
|
"adp": [
|
|
{
|
|
"metrics": [
|
|
{
|
|
"other": {
|
|
"type": "ssvc",
|
|
"content": {
|
|
"timestamp": "2025-05-13T13:23:44.449721Z",
|
|
"id": "CVE-2025-40555",
|
|
"options": [
|
|
{
|
|
"Exploitation": "none"
|
|
},
|
|
{
|
|
"Automatable": "no"
|
|
},
|
|
{
|
|
"Technical Impact": "partial"
|
|
}
|
|
],
|
|
"role": "CISA Coordinator",
|
|
"version": "2.0.3"
|
|
}
|
|
}
|
|
}
|
|
],
|
|
"title": "CISA ADP Vulnrichment",
|
|
"providerMetadata": {
|
|
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
|
"shortName": "CISA-ADP",
|
|
"dateUpdated": "2025-05-13T13:25:06.076Z"
|
|
}
|
|
}
|
|
]
|
|
}
|
|
} |