"cveMetadata": {
|
||
"cveId": "CVE-2024-10386",
|
||
"assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
|
||
"state": "PUBLISHED",
|
||
"assignerShortName": "Rockwell",
|
||
"dateReserved": "2024-10-25T12:38:28.748Z",
|
||
"datePublished": "2024-10-25T17:04:34.000Z",
|
||
"dateUpdated": "2024-10-25T20:17:55.566Z"
|
||
},
|
||
"containers": {
|
||
"cna": {
|
||
"affected": [
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"product": "FactoryTalk ThinManager",
|
||
"vendor": "Rockwell Automation",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "11.2.0-11.2.9"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "12.0.0-12.0.7"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "12.1.0-12.1.8"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.0.0-13.0.5"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.1.0-13.1.3"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "13.2.0-13.2.2"
|
||
},
|
||
{
|
||
"status": "affected",
|
||
"version": "14.0.0"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"credits": [
|
||
{
|
||
"lang": "en",
|
||
"type": "reporter",
|
||
"value": "Tenable Network Security"
|
||
}
|
||
],
|
||
"datePublic": "2024-10-25T17:00:00.000Z",
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"supportingMedia": [
|
||
{
|
||
"base64": false,
|
||
"type": "text/html",
|
||
"value": "<p><b><u>CVE-2024-10386 IMPACT</u></b><u></u></p>\n\n<p>An authentication\nvulnerability exists in the affected product. The vulnerability could allow a\nthreat actor with network access to send crafted messages to the device, potentially\nresulting in database manipulation.</p>"
|
||
}
|
||
],
|
||
"value": "CVE-2024-10386 IMPACT\n\n\n\nAn authentication\nvulnerability exists in the affected product. The vulnerability could allow a\nthreat actor with network access to send crafted messages to the device, potentially\nresulting in database manipulation."
|
||
}
|
||
],
|
||
"impacts": [
|
||
{
|
||
"capecId": "CAPEC-153",
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"value": "CAPEC-153 Input Data Manipulation"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"metrics": [
|
||
{
|
||
"cvssV4_0": {
|
||
"Automatable": "NOT_DEFINED",
|
||
"Recovery": "NOT_DEFINED",
|
||
"Safety": "NOT_DEFINED",
|
||
"attackComplexity": "LOW",
|
||
"attackRequirements": "NONE",
|
||
"attackVector": "NETWORK",
|
||
"baseScore": 9.3,
|
||
"baseSeverity": "CRITICAL",
|
||
"privilegesRequired": "NONE",
|
||
"providerUrgency": "NOT_DEFINED",
|
||
"subAvailabilityImpact": "NONE",
|
||
"subConfidentialityImpact": "NONE",
|
||
"subIntegrityImpact": "NONE",
|
||
"userInteraction": "NONE",
|
||
"valueDensity": "NOT_DEFINED",
|
||
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
|
||
"version": "4.0",
|
||
"vulnAvailabilityImpact": "HIGH",
|
||
"vulnConfidentialityImpact": "HIGH",
|
||
"vulnIntegrityImpact": "HIGH",
|
||
"vulnerabilityResponseEffort": "NOT_DEFINED"
|
||
},
|
||
"format": "CVSS",
|
||
"scenarios": [
|
||
{
|
||
"lang": "en",
|
||
"value": "GENERAL"
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"cvssV3_1": {
|
||
"attackComplexity": "LOW",
|
||
"attackVector": "NETWORK",
|
||
"availabilityImpact": "HIGH",
|
||
"baseScore": 9.8,
|
||
"baseSeverity": "CRITICAL",
|
||
"confidentialityImpact": "HIGH",
|
||
"integrityImpact": "HIGH",
|
||
"privilegesRequired": "NONE",
|
||
"scope": "UNCHANGED",
|
||
"userInteraction": "NONE",
|
||
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
|
||
"version": "3.1"
|
||
},
|
||
"format": "CVSS",
|
||
"scenarios": [
|
||
{
|
||
"lang": "en",
|
||
"value": "GENERAL"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"problemTypes": [
|
||
{
|
||
"descriptions": [
|
||
{
|
||
"cweId": "CWE-306",
|
||
"description": "CWE-306 Missing Authentication for Critical Function",
|
||
"lang": "en",
|
||
"type": "CWE"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"providerMetadata": {
|
||
"orgId": "b73dd486-f505-4403-b634-40b078b177f0",
|
||
"shortName": "Rockwell",
|
||
"dateUpdated": "2024-10-25T17:04:34.000Z"
|
||
},
|
||
"references": [
|
||
{
|
||
"url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1708.html"
|
||
}
|
||
],
|
||
"solutions": [
|
||
{
|
||
"lang": "en",
|
||
"supportingMedia": [
|
||
{
|
||
"base64": false,
|
||
"type": "text/html",
|
||
"value": "<span style=\"background-color: var(--wht);\">· \nIf able,\nnavigate to the </span><a target=\"_blank\" rel=\"nofollow\" href=\"https://thinmanager.com/downloads/\">ThinManager® download site</a><span style=\"background-color: var(--wht);\"> and upgrade to a corrected version of ThinManager®</span>\n\n<br><br><p>11.2.10<br>\n</p>\n\n<p>12.0.8<br>\n</p>\n\n<p>12.1.9<br>\n</p>\n\n<p>13.0.6 </p>\n\n\n\n<p>13.1.4 </p>\n\n\n\n<p>13.2.3 </p>\n\n\n\n<p>14.0.1</p>\n\n\n\n\n\n<br>"
|
||
}
|
||
],
|
||
"value": "· \nIf able,\nnavigate to the ThinManager® download site https://thinmanager.com/downloads/ and upgrade to a corrected version of ThinManager®\n\n\n\n11.2.10\n\n\n\n\n\n12.0.8\n\n\n\n\n\n12.1.9\n\n\n\n\n\n13.0.6 \n\n\n\n\n\n13.1.4 \n\n\n\n\n\n13.2.3 \n\n\n\n\n\n14.0.1"
|
||
}
|
||
],
|
||
"source": {
|
||
"discovery": "EXTERNAL"
|
||
},
|
||
"title": "Rockwell Automation FactoryTalk ThinManager Authentication Vulnerability",
|
||
"workarounds": [
|
||
{
|
||
"lang": "en",
|
||
"supportingMedia": [
|
||
{
|
||
"base64": false,
|
||
"type": "text/html",
|
||
"value": "<p><span style=\"background-color: var(--wht);\">· \nIf able,\nnavigate to the </span><a target=\"_blank\" rel=\"nofollow\" href=\"https://thinmanager.com/downloads/\">ThinManager® download site</a><span style=\"background-color: var(--wht);\"> and upgrade to a corrected version of ThinManager®</span></p>\n\n<p>· \nImplement\nnetwork hardening for ThinManager® Device(s) by limiting communications to TCP\n2031 to only the devices that need connection to the ThinManager®</p>\n\n<p>· \nFor\ninformation on how to mitigate Security Risks on industrial automation control\nsystems, we encourage customers to implement our suggested <a target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\">security best\npractices</a> to\nminimize the risk of the vulnerability.</p>\n\n\n\n\n\n<br>"
|
||
}
|
||
],
|
||
"value": "· \nIf able,\nnavigate to the ThinManager® download site https://thinmanager.com/downloads/ and upgrade to a corrected version of ThinManager®\n\n\n\n· \nImplement\nnetwork hardening for ThinManager® Device(s) by limiting communications to TCP\n2031 to only the devices that need connection to the ThinManager®\n\n\n\n· \nFor\ninformation on how to mitigate Security Risks on industrial automation control\nsystems, we encourage customers to implement our suggested security best\npractices to\nminimize the risk of the vulnerability."
|
||
}
|
||
],
|
||
"x_generator": {
|
||
"engine": "Vulnogram 0.2.0"
|
||
}
|
||
},
|
||
"adp": [
|
||
{
|
||
"affected": [
|
||
{
|
||
"vendor": "rockwellautomation",
|
||
"product": "thinmanager",
|
||
"cpes": [
|
||
"cpe:2.3:a:rockwellautomation:thinmanager:*:*:*:*:*:*:*:*"
|
||
],
|
||
"defaultStatus": "unaffected",
|
||
"versions": [
|
||
{
|
||
"version": "11.2.0",
|
||
"status": "affected",
|
||
"lessThanOrEqual": "11.2.9",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"version": "12.0.0",
|
||
"status": "affected",
|
||
"lessThanOrEqual": "12.0.7",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"version": "12.1.0",
|
||
"status": "affected",
|
||
"lessThanOrEqual": "12.1.8",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"version": "13.0.0",
|
||
"status": "affected",
|
||
"lessThanOrEqual": "13.0.5",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"version": "13.1.0",
|
||
"status": "affected",
|
||
"lessThanOrEqual": "13.1.3",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"version": "13.2.0",
|
||
"status": "affected",
|
||
"lessThanOrEqual": "13.2.2",
|
||
"versionType": "custom"
|
||
},
|
||
{
|
||
"version": "14.0.0",
|
||
"status": "affected"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"metrics": [
|
||
{
|
||
"other": {
|
||
"type": "ssvc",
|
||
"content": {
|
||
"timestamp": "2024-10-25T20:14:39.256573Z",
|
||
"id": "CVE-2024-10386",
|
||
"options": [
|
||
{
|
||
"Exploitation": "none"
|
||
},
|
||
{
|
||
"Automatable": "yes"
|
||
},
|
||
{
|
||
"Technical Impact": "total"
|
||
}
|
||
],
|
||
"role": "CISA Coordinator",
|
||
"version": "2.0.3"
|
||
}
|
||
}
|
||
}
|
||
],
|
||
"title": "CISA ADP Vulnrichment",
|
||
"providerMetadata": {
|
||
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
||
"shortName": "CISA-ADP",
|
||
"dateUpdated": "2024-10-25T20:17:55.566Z"
|
||
}
|
||
}
|
||
]
|
||
}
|
||
} |