"dataType": "CVE_RECORD",
|
||
"dataVersion": "5.1",
|
||
"cveMetadata": {
|
||
"cveId": "CVE-2023-0811",
|
||
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
|
||
"state": "PUBLISHED",
|
||
"assignerShortName": "icscert",
|
||
"dateReserved": "2023-02-13T15:41:55.590Z",
|
||
"datePublished": "2023-03-16T17:41:25.525Z",
|
||
"dateUpdated": "2025-01-16T21:42:32.824Z"
|
||
},
|
||
"containers": {
|
||
"cna": {
|
||
"affected": [
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CJ2H-CPU6 □ -EIP",
|
||
"product": "CJ1M SYSMAC CJ-series",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CJ2H-CPU6 □",
|
||
"product": "CJ1M SYSMAC CJ-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CJ2M-CPU □ □",
|
||
"product": "CJ1M SYSMAC CJ-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CJ1G-CPU □ □ P",
|
||
"product": "CJ1M SYSMAC CJ-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1H-CPU □ □ H",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1G-CPU □ □ H",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1D-CPU □ □ HA",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1D-CPU □ □ H",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1D-CPU □ □ SA",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1D-CPU □ □ S",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CS1D-CPU □ □ P",
|
||
"product": "CJ1M SYSMAC CS-series ",
|
||
"vendor": "Omron ",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP2E-E □ □ D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP2E-S □ □ D □- □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP2E-N □ □ D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1H-X40D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1H-XA40D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1H-Y20DT-D",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1L-EL20D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1L-EM □ □ D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1L-L □ □ D □- □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1L-M □ □ D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1E-E □ □ D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"packageName": "CP1E-NA □ □ D □ - □",
|
||
"product": "CJ1M SYSMAC CP-series",
|
||
"vendor": "Omron",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All versions "
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"credits": [
|
||
{
|
||
"lang": "en",
|
||
"type": "finder",
|
||
"user": "00000000-0000-4000-9000-000000000000",
|
||
"value": "Sam Hanson of Dragos reported these vulnerabilities to CISA. "
|
||
}
|
||
],
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"supportingMedia": [
|
||
{
|
||
"base64": false,
|
||
"type": "text/html",
|
||
"value": "\n\n<span style=\"background-color: rgb(255, 255, 255);\">Omron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored. If an adversary issues a PROGRAM AREA WRITE command to a specific memory region, they could overwrite the password. This may lead to disabling UM protections or setting a non-ASCII password (non-keyboard characters) and preventing an engineer from viewing or modifying the user program. </span>\n\n"
|
||
}
|
||
],
|
||
"value": "\nOmron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored. If an adversary issues a PROGRAM AREA WRITE command to a specific memory region, they could overwrite the password. This may lead to disabling UM protections or setting a non-ASCII password (non-keyboard characters) and preventing an engineer from viewing or modifying the user program. \n\n"
|
||
}
|
||
],
|
||
"metrics": [
|
||
{
|
||
"cvssV3_1": {
|
||
"attackComplexity": "LOW",
|
||
"attackVector": "NETWORK",
|
||
"availabilityImpact": "HIGH",
|
||
"baseScore": 9.1,
|
||
"baseSeverity": "CRITICAL",
|
||
"confidentialityImpact": "NONE",
|
||
"integrityImpact": "HIGH",
|
||
"privilegesRequired": "NONE",
|
||
"scope": "UNCHANGED",
|
||
"userInteraction": "NONE",
|
||
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H",
|
||
"version": "3.1"
|
||
},
|
||
"format": "CVSS",
|
||
"scenarios": [
|
||
{
|
||
"lang": "en",
|
||
"value": "GENERAL"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"problemTypes": [
|
||
{
|
||
"descriptions": [
|
||
{
|
||
"cweId": "CWE-284",
|
||
"description": "CWE-284 Improper Access Control ",
|
||
"lang": "en",
|
||
"type": "CWE"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"providerMetadata": {
|
||
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
|
||
"shortName": "icscert",
|
||
"dateUpdated": "2023-03-16T17:45:14.919Z"
|
||
},
|
||
"references": [
|
||
{
|
||
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-073-01"
|
||
},
|
||
{
|
||
"url": "https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf"
|
||
}
|
||
],
|
||
"source": {
|
||
"discovery": "UNKNOWN"
|
||
},
|
||
"workarounds": [
|
||
{
|
||
"lang": "en",
|
||
"supportingMedia": [
|
||
{
|
||
"base64": false,
|
||
"type": "text/html",
|
||
"value": "\n\n<p>OMRON has released the following countermeasures for users to implement: </p><ul><li>Enable the hardware switch to prohibit writing UM (DIP switch on front panel of the CPU Unit) </li><li>Set UM read protection password and “Prohibit from overwriting to a protected program “option. </li></ul><p>If the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures: </p><p>Security measures to prevent unauthorized access: </p><ul><li>If the following products and versions are used, the risk of attacks by an attacker via the network can be reduced by taking the following measures. <ul><li>Enable the FINS write protection function. </li><li>Select the Protect by IP Address </li></ul></li><li>Minimize connection of control systems and equipment to open networks, so that untrusted devices will be unable to access them. </li><li>Implement firewalls (by shutting down unused communications ports, limiting communications hosts, limiting access to FINS port (9600)) and isolate them from the IT network. </li><li>Use a virtual private network (VPN) for remote access to control systems and equipment. </li><li>Use strong passwords and change them frequently. </li><li>Install physical controls so that only authorized personnel can access control systems and equipment. </li><li>Scan virus to ensure safety of any USB drives or similar devices before connecting them to systems and devices. </li><li>Enforce multifactor authentication to all devices with remote access to control systems and equipment whenever possible. </li><li>Anti-virus protection <ul><li>Protect any PC with access to the control system against malware and ensure installation and maintenance of up-to-date commercial grade anti-virus software protection. </li></ul></li><li>Data input and output protection <ul><li>Validation processing such as backup and range check to cope with unintentional modification of input/output data to control systems and devices. </li></ul></li><li>Data recovery <ul><li>Periodical data backup and maintenance to prepare for data loss. </li></ul></li></ul><p>For more information, see Omron’s <a target=\"_blank\" rel=\"nofollow\" href=\"https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf\">Security Advisory</a>.</p><br>\n\n<br>"
|
||
}
|
||
],
|
||
"value": "\nOMRON has released the following countermeasures for users to implement: \n\n * Enable the hardware switch to prohibit writing UM (DIP switch on front panel of the CPU Unit) \n * Set UM read protection password and “Prohibit from overwriting to a protected program “option. \n\n\nIf the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures: \n\nSecurity measures to prevent unauthorized access: \n\n * If the following products and versions are used, the risk of attacks by an attacker via the network can be reduced by taking the following measures. * Enable the FINS write protection function. \n * Select the Protect by IP Address \n\n\n\n * Minimize connection of control systems and equipment to open networks, so that untrusted devices will be unable to access them. \n * Implement firewalls (by shutting down unused communications ports, limiting communications hosts, limiting access to FINS port (9600)) and isolate them from the IT network. \n * Use a virtual private network (VPN) for remote access to control systems and equipment. \n * Use strong passwords and change them frequently. \n * Install physical controls so that only authorized personnel can access control systems and equipment. \n * Scan virus to ensure safety of any USB drives or similar devices before connecting them to systems and devices. \n * Enforce multifactor authentication to all devices with remote access to control systems and equipment whenever possible. \n * Anti-virus protection * Protect any PC with access to the control system against malware and ensure installation and maintenance of up-to-date commercial grade anti-virus software protection. \n\n\n\n * Data input and output protection * Validation processing such as backup and range check to cope with unintentional modification of input/output data to control systems and devices. \n\n\n\n * Data recovery * Periodical data backup and maintenance to prepare for data loss. \n\n\n\n\n\nFor more information, see Omron’s Security Advisory https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf .\n\n\n\n\n\n"
|
||
}
|
||
],
|
||
"x_generator": {
|
||
"engine": "Vulnogram 0.1.0-dev"
|
||
}
|
||
},
|
||
"adp": [
|
||
{
|
||
"providerMetadata": {
|
||
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
|
||
"shortName": "CVE",
|
||
"dateUpdated": "2024-08-02T05:24:34.505Z"
|
||
},
|
||
"title": "CVE Program Container",
|
||
"references": [
|
||
{
|
||
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-073-01",
|
||
"tags": [
|
||
"x_transferred"
|
||
]
|
||
},
|
||
{
|
||
"url": "https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf",
|
||
"tags": [
|
||
"x_transferred"
|
||
]
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"metrics": [
|
||
{
|
||
"other": {
|
||
"type": "ssvc",
|
||
"content": {
|
||
"timestamp": "2025-01-16T20:56:16.921497Z",
|
||
"id": "CVE-2023-0811",
|
||
"options": [
|
||
{
|
||
"Exploitation": "none"
|
||
},
|
||
{
|
||
"Automatable": "yes"
|
||
},
|
||
{
|
||
"Technical Impact": "partial"
|
||
}
|
||
],
|
||
"role": "CISA Coordinator",
|
||
"version": "2.0.3"
|
||
}
|
||
}
|
||
}
|
||
],
|
||
"title": "CISA ADP Vulnrichment",
|
||
"providerMetadata": {
|
||
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
||
"shortName": "CISA-ADP",
|
||
"dateUpdated": "2025-01-16T21:42:32.824Z"
|
||
}
|
||
}
|
||
]
|
||
}
|
||
} |