190 lines
7.9 KiB
JSON
190 lines
7.9 KiB
JSON
{
|
||
"dataType": "CVE_RECORD",
|
||
"dataVersion": "5.1",
|
||
"cveMetadata": {
|
||
"cveId": "CVE-2022-46670",
|
||
"assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
|
||
"state": "PUBLISHED",
|
||
"assignerShortName": "Rockwell",
|
||
"requesterUserId": "20b06643-9bf3-4d1d-a98d-f8db99f95a31",
|
||
"dateReserved": "2022-12-06T15:27:58.542Z",
|
||
"datePublished": "2022-12-16T20:12:22.414Z",
|
||
"dateUpdated": "2025-04-17T14:35:29.173Z"
|
||
},
|
||
"containers": {
|
||
"cna": {
|
||
"affected": [
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"product": "MicroLogix 1100 & 1400 Controllers",
|
||
"vendor": "Rockwell Automation",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "All"
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"product": "MicroLogix 1400-B/C",
|
||
"vendor": "Rockwell Automation",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "21.007 and below"
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"defaultStatus": "unaffected",
|
||
"product": "MicroLogix 1400-A",
|
||
"vendor": "Rockwell Automation",
|
||
"versions": [
|
||
{
|
||
"status": "affected",
|
||
"version": "7.000 and below"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"credits": [
|
||
{
|
||
"lang": "en",
|
||
"type": "finder",
|
||
"user": "00000000-0000-4000-9000-000000000000",
|
||
"value": "Ryan Pickren, a security researcher from Georgia Institute of Technology"
|
||
}
|
||
],
|
||
"datePublic": "2022-12-13T15:00:00.000Z",
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"supportingMedia": [
|
||
{
|
||
"base64": false,
|
||
"type": "text/html",
|
||
"value": "\n\n<span style=\"background-color: rgb(255, 255, 255);\">Rockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution. The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website. </span>\n\n"
|
||
}
|
||
],
|
||
"value": "\nRockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution. The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website. \n\n"
|
||
}
|
||
],
|
||
"impacts": [
|
||
{
|
||
"capecId": "CAPEC-63",
|
||
"descriptions": [
|
||
{
|
||
"lang": "en",
|
||
"value": "CAPEC-63 Cross-Site Scripting (XSS)"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"metrics": [
|
||
{
|
||
"cvssV3_1": {
|
||
"attackComplexity": "LOW",
|
||
"attackVector": "NETWORK",
|
||
"availabilityImpact": "LOW",
|
||
"baseScore": 7.1,
|
||
"baseSeverity": "HIGH",
|
||
"confidentialityImpact": "LOW",
|
||
"integrityImpact": "LOW",
|
||
"privilegesRequired": "NONE",
|
||
"scope": "CHANGED",
|
||
"userInteraction": "REQUIRED",
|
||
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L",
|
||
"version": "3.1"
|
||
},
|
||
"format": "CVSS",
|
||
"scenarios": [
|
||
{
|
||
"lang": "en",
|
||
"value": "GENERAL"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"problemTypes": [
|
||
{
|
||
"descriptions": [
|
||
{
|
||
"cweId": "CWE-79",
|
||
"description": "CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')",
|
||
"lang": "en",
|
||
"type": "CWE"
|
||
}
|
||
]
|
||
}
|
||
],
|
||
"providerMetadata": {
|
||
"orgId": "b73dd486-f505-4403-b634-40b078b177f0",
|
||
"shortName": "Rockwell",
|
||
"dateUpdated": "2022-12-16T20:12:22.414Z"
|
||
},
|
||
"references": [
|
||
{
|
||
"url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137679"
|
||
}
|
||
],
|
||
"source": {
|
||
"discovery": "UNKNOWN"
|
||
},
|
||
"title": "Rockwell Automation MicroLogix 1100 & 1400 Vulnerable to Cross-Site Scripting Attack",
|
||
"x_generator": {
|
||
"engine": "Vulnogram 0.1.0-dev"
|
||
}
|
||
},
|
||
"adp": [
|
||
{
|
||
"providerMetadata": {
|
||
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
|
||
"shortName": "CVE",
|
||
"dateUpdated": "2024-08-03T14:39:38.680Z"
|
||
},
|
||
"title": "CVE Program Container",
|
||
"references": [
|
||
{
|
||
"url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137679",
|
||
"tags": [
|
||
"x_transferred"
|
||
]
|
||
}
|
||
]
|
||
},
|
||
{
|
||
"metrics": [
|
||
{
|
||
"other": {
|
||
"type": "ssvc",
|
||
"content": {
|
||
"timestamp": "2025-04-17T14:35:20.399901Z",
|
||
"id": "CVE-2022-46670",
|
||
"options": [
|
||
{
|
||
"Exploitation": "none"
|
||
},
|
||
{
|
||
"Automatable": "no"
|
||
},
|
||
{
|
||
"Technical Impact": "partial"
|
||
}
|
||
],
|
||
"role": "CISA Coordinator",
|
||
"version": "2.0.3"
|
||
}
|
||
}
|
||
}
|
||
],
|
||
"title": "CISA ADP Vulnrichment",
|
||
"providerMetadata": {
|
||
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
||
"shortName": "CISA-ADP",
|
||
"dateUpdated": "2025-04-17T14:35:29.173Z"
|
||
}
|
||
}
|
||
]
|
||
}
|
||
} |