Files
vuln-cve/data/2020/24xxx/CVE-2020-24681.json
T

231 lines
9.8 KiB
JSON

{
"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"cveMetadata": {
"cveId": "CVE-2020-24681",
"assignerOrgId": "2b718523-d88f-4f37-9bbd-300c20644bf9",
"state": "PUBLISHED",
"assignerShortName": "ABB",
"dateReserved": "2020-08-26T00:00:00.000Z",
"datePublished": "2024-02-02T06:58:24.173Z",
"dateUpdated": "2025-05-09T17:52:17.145Z"
},
"containers": {
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Automation Studio",
"vendor": "B&R Industrial Automation",
"versions": [
{
"lessThanOrEqual": "4.6.x",
"status": "affected",
"version": "4.6.0",
"versionType": "custom"
},
{
"lessThan": "4.7.7 SP",
"status": "affected",
"version": "4.7.0",
"versionType": "custom"
},
{
"lessThan": "4.8.6 SP",
"status": "affected",
"version": "4.8.0",
"versionType": "custom"
},
{
"lessThan": "4.9.4 SP",
"status": "affected",
"version": "4.9.0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "NET/PVI",
"vendor": "B&R Industrial Automation",
"versions": [
{
"lessThanOrEqual": "4.6.x",
"status": "affected",
"version": "4.6.0",
"versionType": "custom"
},
{
"lessThan": "4.7.7",
"status": "affected",
"version": "4.7.0",
"versionType": "custom"
},
{
"lessThan": "4.8.6",
"status": "affected",
"version": "4.8.0",
"versionType": "custom"
},
{
"lessThan": "4.9.4",
"status": "affected",
"version": "4.9.0",
"versionType": "custom"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "finder",
"user": "00000000-0000-4000-9000-000000000000",
"value": "B&R would like to thank the following for working with us to help protect our customers: Mr. Andrew Hofmans"
}
],
"datePublic": "2021-11-29T18:30:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Incorrect Permission Assignment for Critical Resource vulnerability in B&amp;R Industrial Automation Automation Studio allows Privilege Escalation.<p>This issue affects Automation Studio: from 4.6.0 through 4.6.X, from 4.7.0 before 4.7.7 SP, from 4.8.0 before 4.8.6 SP, from 4.9.0 before 4.9.4 SP.</p>"
}
],
"value": "Incorrect Permission Assignment for Critical Resource vulnerability in B&R Industrial Automation Automation Studio allows Privilege Escalation.This issue affects Automation Studio: from 4.6.0 through 4.6.X, from 4.7.0 before 4.7.7 SP, from 4.8.0 before 4.8.6 SP, from 4.9.0 before 4.9.4 SP.\n\n"
}
],
"impacts": [
{
"capecId": "CAPEC-233",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-233 Privilege Escalation"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 8.2,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "CHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-732",
"description": "CWE-732 Incorrect Permission Assignment for Critical Resource",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"orgId": "2b718523-d88f-4f37-9bbd-300c20644bf9",
"shortName": "ABB",
"dateUpdated": "2024-02-02T06:58:24.173Z"
},
"references": [
{
"url": "https://www.br-automation.com/fileadmin/2021-14-BR-AS-NET-PVI-Service-Issues-c3710fbf.pdf"
}
],
"source": {
"discovery": "UNKNOWN"
},
"title": "Automation Studio and PVI Multiple incorrect permission assignments for services",
"workarounds": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\nB&amp;R has identified the following specific workarounds and mitigations.\nUsers of B&amp;R Automation Studio and PVI may manually reconfigure permission settings on these \nservices to allow modification only for privileged users.\nAdditionally, it is recommended to limit access to the workstation running B&amp;R Automation Studio and PVI \nto authorized users.\n\n\n<br>"
}
],
"value": "\nB&R has identified the following specific workarounds and mitigations.\nUsers of B&R Automation Studio and PVI may manually reconfigure permission settings on these \nservices to allow modification only for privileged users.\nAdditionally, it is recommended to limit access to the workstation running B&R Automation Studio and PVI \nto authorized users.\n\n\n\n"
}
],
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
},
"adp": [
{
"providerMetadata": {
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE",
"dateUpdated": "2024-08-04T15:19:09.083Z"
},
"title": "CVE Program Container",
"references": [
{
"url": "https://www.br-automation.com/fileadmin/2021-14-BR-AS-NET-PVI-Service-Issues-c3710fbf.pdf",
"tags": [
"x_transferred"
]
}
]
},
{
"metrics": [
{
"other": {
"type": "ssvc",
"content": {
"timestamp": "2024-02-02T17:22:16.797450Z",
"id": "CVE-2020-24681",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
}
],
"title": "CISA ADP Vulnrichment",
"providerMetadata": {
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP",
"dateUpdated": "2025-05-09T17:52:17.145Z"
}
}
]
}
}