"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"cveMetadata": {
"cveId": "CVE-2025-9042",
"assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
"state": "PUBLISHED",
"assignerShortName": "Rockwell",
"dateReserved": "2025-08-14T13:58:45.428Z",
"datePublished": "2025-08-14T14:23:58.491Z",
"dateUpdated": "2025-08-14T15:02:18.647Z"
},
"containers": {
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "FLEX 5000 I/O",
"vendor": "Rockwell Automation",
"versions": [
{
"status": "affected",
"version": "Version 2.011 or below"
}
]
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "<span style=\"background-color: rgb(255, 255, 255);\">\n\n<span style=\"background-color: rgb(255, 255, 255);\">A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.</span>\n\n</span>"
}
],
"value": "A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle."
}
],
"metrics": [
{
"cvssV4_0": {
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"attackVector": "NETWORK",
"baseScore": 8.7,
"baseSeverity": "HIGH",
"privilegesRequired": "NONE",
"providerUrgency": "NOT_DEFINED",
"subAvailabilityImpact": "NONE",
"subConfidentialityImpact": "NONE",
"subIntegrityImpact": "NONE",
"userInteraction": "NONE",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N",
"version": "4.0",
"vulnAvailabilityImpact": "HIGH",
"vulnConfidentialityImpact": "NONE",
"vulnIntegrityImpact": "NONE",
"vulnerabilityResponseEffort": "NOT_DEFINED"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-1287",
"description": "CWE-1287: Improper Validation of Specified Type of Input",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"orgId": "b73dd486-f505-4403-b634-40b078b177f0",
"shortName": "Rockwell",
"dateUpdated": "2025-08-14T15:02:18.647Z"
},
"references": [
{
"url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1737.html"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Upgrade to version 2.012 or later"
}
],
"value": "Upgrade to version 2.012 or later"
}
],
"source": {
"advisory": "SD1737",
"discovery": "INTERNAL"
},
"title": "Rockwell Automation FLEX 5000 I/O - Module Fault",
"x_generator": {
"engine": "Vulnogram 0.2.0"
}
},
"adp": [
{
"metrics": [
{
"other": {
"type": "ssvc",
"content": {
"timestamp": "2025-08-14T14:51:36.300478Z",
"id": "CVE-2025-9042",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "yes"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
}
],
"title": "CISA ADP Vulnrichment",
"providerMetadata": {
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP",
"dateUpdated": "2025-08-14T14:51:42.178Z"
}
}
]
}
}