Files
vuln-cve/data/2023/2xxx/CVE-2023-2071.json
T

180 lines
8.2 KiB
JSON
Raw Blame History

This file contains invisible Unicode characters
This file contains invisible Unicode characters that are indistinguishable to humans but may be processed differently by a computer. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
{
"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"cveMetadata": {
"cveId": "CVE-2023-2071",
"assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
"state": "PUBLISHED",
"assignerShortName": "Rockwell",
"dateReserved": "2023-04-14T18:04:01.758Z",
"datePublished": "2023-09-12T13:12:42.386Z",
"dateUpdated": "2024-09-25T20:05:52.107Z"
},
"containers": {
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Fa",
"vendor": "Rockwell Automation",
"versions": [
{
"status": "affected",
"version": "<=13.0"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "finder",
"user": "00000000-0000-4000-9000-000000000000",
"value": " Rockwell Automation would like to thank Yuval Gordon, CPS Research, and the Microsoft Threat Intelligence Community for reporting this vulnerability to us."
}
],
"datePublic": "2023-09-12T13:00:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\n<span style=\"background-color: rgb(255, 255, 255);\">Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. &nbsp;The device has the functionality, through a CIP class, to execute exported functions from libraries. &nbsp;There is a routine that restricts it to execute specific functions from two dynamic link library files. &nbsp;By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.</span>\n\n"
}
],
"value": "\nRockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.\n\n"
}
],
"impacts": [
{
"capecId": "CAPEC-641",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-641 DLL Side-Loading"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-20",
"description": "CWE-20 Improper Input Validation",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"orgId": "b73dd486-f505-4403-b634-40b078b177f0",
"shortName": "Rockwell",
"dateUpdated": "2023-09-12T13:12:42.386Z"
},
"references": [
{
"url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\n<ul><li>Install the security patches for the respective versions referencing <a target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139946\">BF29493 - Patch: FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0</a>.</li></ul>\n\n<br>"
}
],
"value": "\n * Install the security patches for the respective versions referencing BF29493 - Patch: FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139946 .\n\n\n\n\n\n"
}
],
"source": {
"discovery": "UNKNOWN"
},
"title": "FactoryTalk View Machine Edition Vulnerable to Remote Code Execution",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
},
"adp": [
{
"providerMetadata": {
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE",
"dateUpdated": "2024-08-02T06:12:19.927Z"
},
"title": "CVE Program Container",
"references": [
{
"url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724",
"tags": [
"x_transferred"
]
}
]
},
{
"metrics": [
{
"other": {
"type": "ssvc",
"content": {
"timestamp": "2024-09-25T20:05:40.334404Z",
"id": "CVE-2023-2071",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
}
],
"title": "CISA ADP Vulnrichment",
"providerMetadata": {
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP",
"dateUpdated": "2024-09-25T20:05:52.107Z"
}
}
]
}
}