211 lines
8.5 KiB
JSON
211 lines
8.5 KiB
JSON
{
|
|
"dataType": "CVE_RECORD",
|
|
"dataVersion": "5.1",
|
|
"cveMetadata": {
|
|
"cveId": "CVE-2022-4608",
|
|
"assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17",
|
|
"state": "PUBLISHED",
|
|
"assignerShortName": "Hitachi Energy",
|
|
"dateReserved": "2022-12-19T09:46:30.033Z",
|
|
"datePublished": "2023-07-26T05:26:42.720Z",
|
|
"dateUpdated": "2025-03-05T18:46:44.864Z"
|
|
},
|
|
"containers": {
|
|
"cna": {
|
|
"affected": [
|
|
{
|
|
"defaultStatus": "unaffected",
|
|
"product": "RTU500 series",
|
|
"vendor": "Hitachi Energy",
|
|
"versions": [
|
|
{
|
|
"status": "affected",
|
|
"version": "RTU500 series CMU Firmware version 13.3.1"
|
|
},
|
|
{
|
|
"status": "affected",
|
|
"version": "RTU500 series CMU Firmware version 13.3.2"
|
|
},
|
|
{
|
|
"status": "unaffected",
|
|
"version": "RTU500 series CMU Firmware version 13.3.3"
|
|
},
|
|
{
|
|
"status": "unaffected",
|
|
"version": "RTU500 series CMU Firmware version 13.4.1"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"configurations": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled.\n\n<br>"
|
|
}
|
|
],
|
|
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled."
|
|
}
|
|
],
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."
|
|
}
|
|
],
|
|
"value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."
|
|
}
|
|
],
|
|
"impacts": [
|
|
{
|
|
"capecId": "CAPEC-100",
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CAPEC-100 Overflow Buffers"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"metrics": [
|
|
{
|
|
"cvssV3_1": {
|
|
"attackComplexity": "LOW",
|
|
"attackVector": "NETWORK",
|
|
"availabilityImpact": "HIGH",
|
|
"baseScore": 7.5,
|
|
"baseSeverity": "HIGH",
|
|
"confidentialityImpact": "NONE",
|
|
"integrityImpact": "NONE",
|
|
"privilegesRequired": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"userInteraction": "NONE",
|
|
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
|
|
"version": "3.1"
|
|
},
|
|
"format": "CVSS",
|
|
"scenarios": [
|
|
{
|
|
"lang": "en",
|
|
"value": "GENERAL"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"problemTypes": [
|
|
{
|
|
"descriptions": [
|
|
{
|
|
"cweId": "CWE-787",
|
|
"description": "CWE-787 Out-of-bounds Write",
|
|
"lang": "en",
|
|
"type": "CWE"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"providerMetadata": {
|
|
"orgId": "e383dce4-0c27-4495-91c4-0db157728d17",
|
|
"shortName": "Hitachi Energy",
|
|
"dateUpdated": "2024-09-24T15:33:42.351Z"
|
|
},
|
|
"references": [
|
|
{
|
|
"tags": [
|
|
"vendor-advisory"
|
|
],
|
|
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch"
|
|
}
|
|
],
|
|
"solutions": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1.\n\n<br>"
|
|
}
|
|
],
|
|
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1."
|
|
}
|
|
],
|
|
"source": {
|
|
"discovery": "UNKNOWN"
|
|
},
|
|
"workarounds": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used.\n\n<br>"
|
|
}
|
|
],
|
|
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used."
|
|
}
|
|
],
|
|
"x_generator": {
|
|
"engine": "Vulnogram 0.1.0-dev"
|
|
}
|
|
},
|
|
"adp": [
|
|
{
|
|
"providerMetadata": {
|
|
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
|
|
"shortName": "CVE",
|
|
"dateUpdated": "2024-08-03T01:41:45.792Z"
|
|
},
|
|
"title": "CVE Program Container",
|
|
"references": [
|
|
{
|
|
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch",
|
|
"tags": [
|
|
"x_transferred"
|
|
]
|
|
}
|
|
]
|
|
},
|
|
{
|
|
"metrics": [
|
|
{
|
|
"other": {
|
|
"type": "ssvc",
|
|
"content": {
|
|
"timestamp": "2025-03-05T18:38:26.416457Z",
|
|
"id": "CVE-2022-4608",
|
|
"options": [
|
|
{
|
|
"Exploitation": "none"
|
|
},
|
|
{
|
|
"Automatable": "yes"
|
|
},
|
|
{
|
|
"Technical Impact": "partial"
|
|
}
|
|
],
|
|
"role": "CISA Coordinator",
|
|
"version": "2.0.3"
|
|
}
|
|
}
|
|
}
|
|
],
|
|
"title": "CISA ADP Vulnrichment",
|
|
"providerMetadata": {
|
|
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
|
|
"shortName": "CISA-ADP",
|
|
"dateUpdated": "2025-03-05T18:46:44.864Z"
|
|
}
|
|
}
|
|
]
|
|
}
|
|
} |